What Can Our HVAC Engineers in West Ridge Chicago Do For You?

Local MEP Engineering

For more than ten years a great number of construction companies throughout Albany, New York already know that NY Engineers is the engineering company to contact when you’re searching for Mechanical Engineering in NY. What a lot local developers have not realized is the NY-Engineers.Com is also your best choice if you’re looking for HVAC Engineering services in West Ridge Chicago, Illinois. Those who want to learn more about what West Ridge Chicago HVAC design engineers do? It is a unique job with an an extensive list of obligations. An HVAC design contractor will be asked to work through several concundrums to work out the core issue. This task calls for distinct expertise, proficieny, and the capability to handle time cleverly.

The moment an HVAC personel is certified to operate, they may join up with an engineering firm and begin to operate various heating, cooling, and refrigeration systems. Their role is usually to design new and replacement selections according to their client’s requests. Each customer is going to have an exclusive set of wants whether it is related to constructing codes or individual performance anticipations. Making use of this information, the engineer goes on a trek towards creating something that’s energy-efficient, eco-friendly and perfect for the setting it’s likely to be placed in – (industrial, commercial or residential. They are often accountable for the original drawings and overseeing the particular installation.

On the whole, an HVAC engineer in West Ridge Chicago will likely be seen working with a design company or in a consulting firm depending on their numerous years of skill. Many engineers move in to a consulting job because they mature and acquire a better idea of what is expected of them.

Comparing HVAC Technician vs HVAC Engineer

HVAC Engineer and HVAC Technician tend to be confused with each other. But, they have got separate tasks when it comes to handling HVAC systems. It is important to understand the variance both as being a parton also as a professional

An HVAC technician in West Ridge Chicago is a more hands-on job, which implies they are often seen heading to a client’s home to see their existing system. They frequently keep up with the repairs, installations, and general care which is needed every once in awhile. Most of their effort is done in conjunction with the buyer, meaning they have to learn how to communicate with people in the correct manner.

Having an HVAC engineer, they are responsible for designing a fresh HVAC system and ensuring that it fits what a client wants. It must fit precisely what the home owner wants if it involves their setup, property, or everything else linked to new system. They are also brought in to check on HVAC creations to be certain all things are consistent with the latest standards. That is why they may wind up spending time in consulting tasks or at neighborhood engineering companies. That is basically the distinction between both of these career paths; HVAC Technician Versus HVAC Engineer. Even with all of this information you would like additional information on the HVAC Engineering services in West Ridge Chicago, Illinois by NY Engineers you should take a look at our blog.

New West Ridge Chicago HVAC Engineering Related Blog Post

Operating Modes of VRF Systems in HVAC Engineering

Architectural Engineering Colleges

Variable Refrigerant Flow (VRF) is an HVAC engineering (air conditioning) technology that achieves an extremely high efficiency by varying the flow of refrigerant to indoor units, based on the exact demand of each individual area. This ability to control the flow of refrigerant makes VRF systems ideal for applications with varying loads. In addition, VRF systems can also provide space heating, consolidating two building systems in one and saving space.

VRF technology is available in two versions – heat pump systems and heat recovery systems. Heat pump VRF systems can either cool or heat the entire building but cannot perform both functions at the same time. Heat recovery systems do not have this limitation and can serve simultaneous heating and cooling loads, thus leading to 3 different modes of operation:

  • Cooling mode
  • Heating mode
  • Simultaneous cooling & heating, or heat recovery mode

VRF Systems in Cooling Mode

In cooling mode, VRF operation is not very different from that of an air conditioning system: indoor units are supplied with liquid refrigerant, and an expansion valve inside each unit controls the amount of refrigerant flowing through. When refrigerant enters the cooling coil, it undergoes evaporation, removing heat from indoor air and thereby cooling the room. The heat extracted from indoor spaces is then rejected outdoors.

VRF systems are much more efficient than conventional packaged rooftop units (RTU), packaged terminal air conditioners (PTAC) and window units, according to HVAC engineering experts. Ductless mini-split systems and water-cooled chillers offer a similar efficiency in cooling mode but are unable to operate in heating mode.

VRF Systems in Heating Mode

Unlike cooling mode, where indoor units receive liquid refrigerant, here they are supplied with hot gas refrigerant. Gas flow to individual units is controlled with the same electronic expansion valves used for cooling mode, and the heating effect occurs when hot gas undergoes condensation.

The basic principle is still the refrigeration cycle, with the difference that heat is absorbed from outdoors and rejected indoors; in simple terms it is like air-conditioning the cooler outdoor environment to remove heat from it and use it indoors. This operating mode change is made possible with special 4-way reversing valves, which exchange the roles of evaporator and condenser between indoor and outdoor units.

In heating mode, the electric power consumed becomes useful heat, while in cooling mode it is rejected outdoors. Thus, a VRF outdoor unit can operate above 100% of its rated capacity when in heating mode. However, it is also important to note that the capacity may be derated, especially when the system is subject to a large variation in outdoor conditions. Longer piping lengths, longer distances between the outdoor unit and the last indoor unit, and higher vertical separation are some other causes of derating.

VRF Systems in Heat Recovery Mode

A heat recovery system is ideal when simultaneous heating and cooling are required. The greatest efficiency is achieved when the heating and cooling loads are equal, by maximizing the amount of energy transferred from one zone to another using the refrigerant. Heat rejection from cooling spaces can be utilized for space heating in the areas that need it at the same time. Thanks to this configuration, each occupant is free to choose either cooling or heating mode.

Heat recovery systems are very useful when a building has an east-west or south-north orientation with glass façades. East-west and south-north orientations cause a large difference in load requirements for each direction during the morning and evening, providing a chance for the VRF system to operate in simultaneous heating and cooling mode. Heat recovery is particularly useful in buildings with electrical rooms or data centers that need permanent cooling, since they also become a constant source of heat.

Heat Recovery System Piping Configurations in HVAC Engineering

Heat recovery systems come in 2-pipe and 3-pipe configurations, where the 2-pipe system is the option requiring the highest refrigerant flow. To operate with reduced flow, the 3-pipe system has a liquid line, a high-pressure gas line and a low-pressure gas line. The control function is achieved with a Mode Change Unit (MCU) or Mode Selection Box, which has three headers for high-pressure gas, low-pressure gas, and liquid.

  • When there are zones that need space heating, their indoor units work like condensers, supplying heat from the condensation of high-pressure refrigerant gas. After heating, the saturated refrigerant is fed to the liquid header.
  • Liquid refrigerant is then supplied to the units in space cooling mode, where it evaporates and absorbs heat, becoming a low-pressure gas.
  • The low-pressure gas is returned to its respective header and then to the compressor, repeating the cycle.

In this case, the outdoor unit must only provide the balance between heating and cooling – the one that is higher will determine the operating mode of the outdoor unit.

  • If cooling load is higher, the outdoor unit operates as a condenser, rejecting the surplus heat outdoors.
  • If the heating load is higher, the outdoor units operates as an evaporator, drawing from outdoor air the extra heat needed inside.

The best recommendation is locate the MCU in a public access area such as a corridor, thus minimizing noise and disruption for the end user. Maintenance of heat recovery systems is relatively easy, since the outdoor condenser unit is only connected to the MCU, facilitating system separation into upstream and downstream portions.

As per ASHRAE Standard 34-2013, the refrigerant concentration limit (RCL) is 26 lb per 1,000 ft3 of room volume for occupied spaces, and 13 lb per 1,000 ft3 for institutional buildings. This can be easily achieved by locating the units outside of compact rooms. According to Standard 15, a VRF system is classified as a direct system/high-probability system where a refrigerant leak can potentially enter occupied space.

The use of heat recovery systems in VRF proves to be better option, economically and environmentally, in these types of HVAC engineering systems. This spares the building owners from having to install and service two separate systems, while achieving a very high efficiency. With separate systems for space heating and cooling it is impossible to boost efficiency by exchanging heat, even if both systems are very efficient separately.